Back to the Product
Download the Nu-Calgon Product Catalog.
Designed to introduce Micromet Treatment for controlling lime scale formation, corrosion or red iron staining in well-water systems. Holds four pounds of Micromet and can treat up to 400 gallons of water per day for corrosion and red iron water and up to 800 gallons per day when lime scale is the problem. It can also be used to feed a slower dissolving phosphate, 6R Micromet, into large coffee urns or ice machine as well as other water systems using up to 800 gallons of water (6600 lbs. of ice) per day.
To prevent red iron water with Micromet Crystals, the Feeder should be installed before the pressure tank. On deep well pump installations there should be a check valve in the main line between the Feeder and the pump. To inhibit lime scale or control corrosion the Feeder should be installed on the cold water inlet line to the equipment to be treated. If put before a water heater, place far enough away so no hot water will back up into Feeder. Flow should be up through Feeder.
No. 4 Micromet Feeder - Instruction Bulletin